Kamis, 19 Maret 2015

SMARTGEN HAT560 series ATS






HAT560 series ATS controller is intelligent dual-supply module with configurable function, automatic measurement, LCD display, and digital communication. It combines digital, intelligence and networking. Automatic measurement and control can reduce incorrect operation. It is an ideal optio for ATS.
The powerful Microprocessor contained within the unit allows for precision voltage(2-way 3-phase/single phase) measuring and make accurate judgment on abnormal voltage (power lost, over/under voltage, over/under frequency, loss of phase, phase sequence wrong) and control ATS to tranfer after the delay has expired. This controller is suitable for NO Breaking ATS. When 1# is abnormal, the controller will send signal to start genset after the "1# abnormal delay" has expired. "Three remote"(remote control, remote measurement and remote communication) function can be implemented with the help of LINK communication port.

PERFORMANCE AND CHARACTERISTICS
1.System type can set as: Mains (1#) & Generator (2#), Generator (1#) & Mains (2#), Mains (1#) & Mains (2#), Generator (1#) & Generator (2#). 2.132x64 LCD with backlight, optional Chinese and English display, push-button operation.
3.Measure and display 2-way 3 phase Voltage and Frequency.
4.Over/under voltage, loss of phase, reverse phase sequence, over/under frequency protection.
5.Automatic/Manual mode. In manual mode, can force the switch to close or open;
6.All parameters can be set on site. With Two different passwords which ensures authorized staff operation only.
7.During commissioning, the genset can be set either on On-load or Off-load mode.
8.ATS Controller has function of automatic Re-closing.
9.Closing output signal can be set as on intervals or as continuous output.
10.Applicable for ATS of one neutral position, two neutral position and non-position.
11.Applicable for 2 isolated neutral line.
12.Real-time clock (RTC).
13.Event log can record 50 items circularly.
14.Scheduled start & stop generator (can be set as start genset once a day/week/month whether with load or not).
15.Can control two generators to work in a cycle, even the genset running time and crank rest time can be set.
16.Optional AC system or DC system.
17.With standard LINK communication interface. With "remote controlling, remote measuring, remote communication" function by the ModBus communication protocol. Can remote start/stop the genset and remote control the ATS to close or open.
18.Can check the current status of controller (digital input port, digital output port, over voltage, under voltage, over frequency, under frequency etc.).
19.Suitable for various AC systems (3 phase 4-wires, 3-phase 3-wires, single-phase 2-wire, and 2-phase 3-wire)
20.Modular design, self extinguishing ABS plastic shell, pluggable terminal, built-in mounting,compact structure with easy installation.
HAT560 series controller and its main functions are shown as following,
        Function
Type
DC Power Supply AC Power Supply AC Current/Power
HAT560 × ×
HAT560B √ (LN220V) ×
SPECIFICATION
Items Contents
Operating Voltage 1. DC 8.0V~35.0V, continuous power supply.
2. AC170V~270V during AC power L1N1/L2N2 supply.
Power Consumption <3W (Standby mode: ≤2W)
AC Voltage Input AC system HAT560 HAT560B
3P4W (ph-N) AC30V~AC360V AC170V~AC277V
3P3W (ph-ph) AC60V~AC620V Not used
1P2W (ph-N) AC30V~AC360V AC170V~AC277V
2P3W (ph-N) AC30V~AC360V AC170V~AC277V
Rated Frequency 50/60Hz
Close Relay Output 16A  AC250V  Volts free output
Auxiliary Relay Output 1 7A  AC250V  Volts free output
Auxiliary Relay Output 2 7A  AC250V  Volts free output
Auxiliary Relay Output 3 16A  AC250V  Volts free output
Auxiliary Relay Output 4 16A  AC250V  Volts free output
Digital Input GND connect is active.
Communication LINK interface, MODBUS Protocol
Case Dimensions 139mmx120mmx48mm
Panel Cutout 130mmx111mm
Working Conditions Temperature: (-25~+70)°C;   
Humidity: (20~93)%RH
Storage Condition Temperature: (-25~+70)°C
Protection Level IP55 Gasket 
Insulation Strength Apply AC2.2kV voltage between high voltage terminal and low voltage terminal;
The leakage current is not more than 3mA within 1min.
Weight 0.62kg