HAT560 series ATS controller is
intelligent dual-supply module with configurable function, automatic
measurement, LCD display, and digital communication. It combines
digital, intelligence and networking. Automatic measurement and control
can reduce incorrect operation. It is an ideal optio for ATS.
The powerful Microprocessor
contained within the unit allows for precision voltage(2-way
3-phase/single phase) measuring and make accurate judgment on abnormal
voltage (power lost, over/under voltage, over/under frequency, loss of
phase, phase sequence wrong) and control ATS to tranfer after the delay
has expired. This controller is suitable for NO Breaking ATS. When 1# is
abnormal, the controller will send signal to start genset after the "1#
abnormal delay" has expired. "Three remote"(remote control, remote
measurement and remote communication) function can be implemented with
the help of LINK communication port.
PERFORMANCE AND CHARACTERISTICS
1.System type can set as: Mains (1#) & Generator (2#), Generator (1#) & Mains (2#), Mains (1#) & Mains (2#), Generator (1#) & Generator (2#).
2.132x64 LCD with backlight, optional Chinese and English display, push-button operation.
3.Measure and display 2-way 3 phase Voltage and Frequency.
4.Over/under voltage, loss of phase, reverse phase sequence, over/under frequency protection.
5.Automatic/Manual mode. In manual mode, can force the switch to close or open;
6.All parameters can be set on site. With Two different passwords which ensures authorized staff operation only.
7.During commissioning, the genset can be set either on On-load or Off-load mode.
8.ATS Controller has function of automatic Re-closing.
9.Closing output signal can be set as on intervals or as continuous output.
10.Applicable for ATS of one neutral position, two neutral position and non-position.
11.Applicable for 2 isolated neutral line.
12.Real-time clock (RTC).
13.Event log can record 50 items circularly.
14.Scheduled start & stop generator (can be set as start genset once a day/week/month whether with load or not).
15.Can control two generators to work in a cycle, even the genset running time and crank rest time can be set.
16.Optional AC system or DC system.
17.With standard LINK communication interface. With "remote
controlling, remote measuring, remote communication" function by the
ModBus communication protocol. Can remote start/stop the genset and
remote control the ATS to close or open.
18.Can check the current status of controller (digital input port,
digital output port, over voltage, under voltage, over frequency, under
frequency etc.).
19.Suitable for various AC systems (3 phase 4-wires, 3-phase 3-wires, single-phase 2-wire, and 2-phase 3-wire)
20.Modular design, self extinguishing ABS plastic shell, pluggable
terminal, built-in mounting,compact structure with easy installation.
HAT560 series controller and its main functions are shown as following,
Function
Type |
DC Power Supply |
AC Power Supply |
AC Current/Power |
HAT560 |
√ |
× |
× |
HAT560B |
√ |
√ (LN220V) |
× |
SPECIFICATION
Items |
Contents |
Operating Voltage |
1. DC 8.0V~35.0V, continuous power supply.
2. AC170V~270V during AC power L1N1/L2N2 supply. |
Power Consumption |
<3W (Standby mode: ≤2W) |
AC Voltage Input |
AC system |
HAT560 |
HAT560B |
3P4W (ph-N) |
AC30V~AC360V |
AC170V~AC277V |
3P3W (ph-ph) |
AC60V~AC620V |
Not used |
1P2W (ph-N) |
AC30V~AC360V |
AC170V~AC277V |
2P3W (ph-N) |
AC30V~AC360V |
AC170V~AC277V |
Rated Frequency |
50/60Hz |
Close Relay Output |
16A AC250V Volts free output |
Auxiliary Relay Output 1 |
7A AC250V Volts free output |
Auxiliary Relay Output 2 |
7A AC250V Volts free output |
Auxiliary Relay Output 3 |
16A AC250V Volts free output |
Auxiliary Relay Output 4 |
16A AC250V Volts free output |
Digital Input |
GND connect is active. |
Communication |
LINK interface, MODBUS Protocol |
Case Dimensions |
139mmx120mmx48mm |
Panel Cutout |
130mmx111mm |
Working Conditions |
Temperature: (-25~+70)°C;
Humidity: (20~93)%RH |
Storage Condition |
Temperature: (-25~+70)°C |
Protection Level |
IP55 Gasket |
Insulation Strength |
Apply AC2.2kV voltage between high voltage terminal and low voltage terminal;
The leakage current is not more than 3mA within 1min. |
Weight |
0.62kg |